Download Print this page

Huawei NetCol8000-C070 Quick Manual page 4

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:

Advertisement

Model
Configurati
on
NetCol800
Single route 38.3 A/17.3 A
0-C220
Dual route
NetCol800
Single route 38.3 A/17.3 A
0-C260
Dual route
2.2
Pipe Support
1. The height of a U-shaped pipe clamp equals the diameter of the pipe with thermal insulation
foam minus 5 mm. The pipe supports are to be purchased.
2. The material for pipe supports and clamps should meet outdoor application requirements.
3. Install a support every 2500 mm in the straight sections of pipes, and 1000 mm away from each
bending point in the turning section.
Maximum Current
(with Heating and
Humidification/Without
Heating or
Humidification)
Active: 38.3 A/17.3 A
Standby: 17.3 A
Active: 38.3 A/17.3 A
Standby: 17.3 A
Recommended
Switch (with
Heating and
Humidification/W
ithout Heating or
Humidification)
C50/C25
Active: C50/C25
Standby: C25
C50/C25
Active: C50/C25
Standby: C25
4
Cable Diameter
2
2
4 x 6 mm
/4 x 4 mm
2
Active: 4 x 6 mm
/4 x 4
2
mm
2
Standby: 4 x 4 mm
2
2
4 x 6 mm
/4 x 4 mm
2
Active: 4 x 6 mm
/4 x 4
2
mm
2
Standby: 4 x 4 mm