Check Item
Expected Result
The water inlet solenoid valve is secured. The humidifier water
pump is secured reliably and steadily. The wet film humidifier is
(Optional) Wet
secured reliably and steadily. The humidifier float and its
film humidifier
fasteners are secured reliably. Pipes are connected securely
without leakage.
The water has been filled and air has been exhausted. The
hose clamps and cable ties of the condensate water pipe are
Pipe
reliably secured. The water inlet and outlet pipes are properly
connection
installed and secured, without leaks. The water inlet and outlet
pipes are routed smoothly, without bends. The water outlet
pipe has appropriate gradients (1:100 is recommended).
The power voltage is the same as the rated voltage on the
nameplate of the unit. Cables are intact. No open or short
circuits, or incorrect connections occur in electrical loops.
Cable
Power cables, signal cables, and communications cables have
connection
been connected. The rated values of circuit breakers are
correct. Control cables are properly connected. All cables,
connectors, and bolts are secured.
(Optional)
The pressure tube is secured by cable ties. There is no foreign
Differential
matter in pressure tubes. The pressure tubes show no obvious
pressure
bends. The differential pressure sensor is secured reliably and
sensor
steadily. Cables are connected reliably and steadily.
(Optional)
The damper and cabinet are secured reliably and steadily by
Motorized
bolts as required. (Applicable to motorized damper) Cables of
Damper/Gravity
the damper actuator are connected reliably and steadily.
Damper
(Optional)
The water leakage sensor is secured reliably and steadily.
Water leakage
Cables to the water leakage sensor are connected correctly
sensor
and securely.
The cap and cabinet are secured reliably and steadily as
(Optional) Cap
required.
(Optional)
The direct free-cooling plenum and cabinet are secured
Direct free-
reliably and steadily as required. The actuator is reliably and
cooling plenum
securely connected.
6

Equipment Power-On

6.1
Power-On
NOTE
1. Users are classified into admin and operator users, and admin users have more rights than
operator users. The preset password is 000001 for both types of users. For system security
purposes, change the preset password upon first login.
2. A login session automatically expires if no operation is performed in three minutes. It is
recommended that you tap
are complete.
1. Turn on the general switch, fan switch QF4, and electric heater switch QF3 (optional). For a device
that has two power inputs, turn on the active power switch QF1 and standby power switch QF2.
2. Powered on the cabinet.
Select the language: English or Chinese.
Select the date & time settings: date format, date, time, and time zone.
On the home screen, tap Settings > System Settings > T/H Sensor to change temperature and
humidity control types or set points.
at the lower right corner to manually log out after operations
25
Actual Result
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed