Start-Up; Preliminary Check List; Figure 3-1. Typical Integral Primary 10D1475J Data Tag - ABB MINI-MAG 10D1475 Series Instruction Manual

Magnetic flowmeters
Hide thumbs Also See for MINI-MAG 10D1475 Series:
Table of Contents

Advertisement

10D1475 MINI-MAG MAGNETIC FLOWMETER INSTRUCTION MANUAL

3.0 START-UP

The Series 10D1475 MINI-MAG Magnetic Flowmeter (which includes the integral or remote Signal
Converter) is precision calibrated at the factory for the values stated on the instrument tag. If specific
values were not specified, the meter is calibrated at a nominal maximum flow rate and for a 4-20 mA
current output span. Typical instrument data tags are shown in Figures 3-1 & 3-2.
There are no operating controls that require field adjustment unless the full scale range setting was
not specified when the meter was ordered. If a change in the full scale range setting is required, refer
to the Instruction Manual supplied with the 10D1475J & 10D1475S Signal Converters. If no change
is required, the equipment is ready for operation as received.

FIGURE 3-1. TYPICAL INTEGRAL PRIMARY 10D1475J DATA TAG

FIGURE 3-2. TYP. REMOTE PRIMARY 10D1475J & S DATA TAG

3.1 Preliminary Check List

Follow these start up instructions after completing the assembly and installation of the Primary and
Converter:
• Check that the flow direction of the fluid agrees with the flow-direction arrow
on the primary housing.
• Check that the flowmeter is properly grounded. See Section 2.4. Improper
grounding may result in unsatisfactory performance.
• Check that the interconnections agree with the interconnection diagrams
shown in the instruction manuals supplied with the Converter.
• Check that the power supply agrees with the specifications on the data tag.
• Check that the ambient conditions meet the conditions specified in Section
1.4 - Specifications.
START-UP
3-1