FIELDPOINT OPERATING INSTRUCTIONS AND SPECIFICATIONS cFP-2200/2210/2220/2220A Intelligent Real-Time Controllers for Compact FieldPoint Bottom Bottom Front 1 RS-232 Serial Port 9 RJ-45 Ethernet Port 2 (cFP-2220 and 2 RJ-45 Ethernet Port 1 cFP-2220A Only) 3 Removable Compact Flash (cFP-2220 and 10 Reset Button cFP-2220A Only) 11 Power Connector 4 Status LED...
This document describes how to mount the cFP-2200/2210/2220/2220A controllers, how to connect the controllers to networks, and how to use the features of the controllers. This document also contains specifications for the controllers. In this document, the cFP-2200/2210/2220/2220A controllers are referred to inclusively as the cFP-22xx. Safety Guidelines Operate the cFP-22xx only as described in these operating instructions.
Page 4
has the following symbol stamped beside it: . Connect the backplane PE ground terminal to safety ground using 14 AWG (1.6 mm) wire with a ring lug. Use the 5/16 in. panhead screw shipped with the backplane to secure the ring lug to the backplane PE ground terminal. To ensure maximum cooling efficiency, mount the Compact FieldPoint so that the I/O module vents are at the top and bottom, as shown in the following figure:...
Page 6
104.78 mm (4.1 in.) 63.50 mm 127.00 mm (2.5 in.) (5.0 in.) 22.23 mm (0.9 in.) 440.94 mm (17.4 in.) Figure 5. cFP-BP-8, Back View with Dimensions 104.74 mm (4.1 in.) 63.46 mm 127.00 mm (2.5 in.) (5.0 in.) 22.19 mm (0.9 in.) 245.87 mm (9.6 in.)
Page 8
Connect the PE ground terminal on the backplane to safety ground. Caution Disconnect power and make sure that no I/O modules are in the backplane before removing it from the DIN rail. Mounting the Backplane on a Panel The horizontal panel-mount kit has mounting holes on the sides of the backplane and is NI part number 778616-01.
Page 10
34.0 mm (1.34 in.) 178 mm (7.0 in.) 7.6 mm (0.30 in.) 246 mm (9.7 in.) 17.8 mm (0.70 in.) Figure 13. cFP-BP-4 with Vertical Panel-Mount Kit Installed, Front View with Dimensions 33.1 mm (1.31 in.) 374 mm (14.7 in.) 7.6 mm (0.30 in.) 17.8 mm...
Page 12
T IO IN S Figure 16. Installing the Rack-Mount Bracket on the cFP-BP-4 T IO IN S Figure 17. Installing the Rack-Mount Bracket on the cFP-BP-8 cFP-2200/2210/2220/2220A ni.com...
Page 14
Installing the cFP-22xx on the Backplane Make sure that no power is connected to the controller. Make sure that the controller is right side up with the NI logo at the top, and align the captive screws on the controller with the holes on the backplane.
Page 16
Installing Connector Blocks on the Backplane In order to connect I/O modules to input signals or loads, you need to install a cFP-CB-x connector block or other connectibility accessory for each I/O module on the backplane. Use the connector socket to the right of each I/O module socket.
Page 18
If you need to build your own cable, refer to the Cabling section for more information about Ethernet cable wiring connections. The host computer communicates with the controller over a standard Ethernet connection. If the host computer is on a network, you must configure the controller on the same subnet as the host computer.
Page 20
Figure 24. Ferrite Installed with Tie Wrap Connect the positive lead of the power supply to the V1 terminal of the COMBICON connector shipped with the cFP-22xx. Connect the negative lead of the power supply to one of the C terminals of the COMBICON connector.
Page 22
Pin 5 Pin 9 Pin 6 Pin 1 Figure 25. Controller Serial Port Table 1. DB-9 Pin Descriptions Signal COM 2 (cFP-2210, cFP-2220, and cFP-2220A Only) COM 2 is an RS-232 DTE serial port with a 10-position modular jack. The Serial VIs access COM 2 as port 1.
Page 24
cFP-2220 COM 4 FP-1001 FP-1001 RXD– RXD+ TXD– TXD+ RX– TX– RX– TX– 120 Ω 120 Ω 120 Ω 120 Ω Figure 27. Wiring for an RS-485 Network Controlled by the cFP-2220/2220A COM 4 is designed to operate in four-wire mode as shown in Figure 27. You can use COM 4 in two-wire mode, but you must design your application so that it filters out the writes that echo back over the read channels.
USER1 Figure 29. DIP Switches All of the DIP switches are in the OFF position when the controller is shipped from National Instruments. IP RESET Switch Push the IP RESET switch to the ON position and reboot the controller to reset the IP address to .
This usually occurs when the controller runs out of memory. Review your RT VI and check the memory usage. Modify the VI as necessary to solve the memory usage issue. Solid The controller has detected an unrecoverable error. Please contact National Instruments. cFP-2200/2210/2220/2220A ni.com...
Remote Front Panels You may need to monitor and control an embedded VI remotely. The cFP-22xx supports multiple remote front panels for embedded VIs. Users can view the remote front panel using either LabVIEW or a Web browser. Users accessing the remote front panels with a Web browser need to have either Internet Explorer 5.5 Service Pack 2 or later, or Netscape 4.7 or later.
Specifications The following specifications are typical for the –40 to 70 °C operating temperature range unless otherwise noted. Network Network interface ........10BaseT and 100BaseTX Ethernet Compatibility ..........IEEE 802.3 Communication rates ......10 Mbps, 100 Mbps, auto-negotiated Maximum cabling distance.....100 m/segment Memory cFP-2200..........128 MB nonvolatile;...
Torque for screw terminals.....0.5 to 0.6 N · m (4.4 to 5.3 lb · in.) Weight ............278 g (9.8 oz) Safety Voltages Connect only voltages that are within these limits. V terminal to C terminal ......35 V max, Measurement Category I Measurement Category I is for measurements performed on circuits not directly connected to the electrical distribution system referred to as MAINS voltage.
Waste Electrical and Electronic Equipment (WEEE) EU Customers At the end of their life cycle, all products must be sent to a WEEE recycling center. For more information about WEEE recycling centers and National Instruments WEEE initiatives, visit ni.com/environment/weee.htm RoHS...
Hazardous Locations U.S. (UL) ..........Class I, Division 2, Groups A, B, C, D, T4; Class I, Zone 2, AEx nL IIC T4 Canada (C-UL) ........Class I, Division 2, Groups A, B, C, D, T4; Class I, Zone 2, Ex nL IIC T4 Europe (DEMKO) cFP-2200/2210/2220A only ....Ex nL IIC T4 Environmental...
Where to Go for Support The National Instruments Web site is your complete resource for technical support. At you have access to everything from ni.com/support troubleshooting and application development self-help resources to email and phone assistance from NI Application Engineers.
Page 40
Instruments trademarks. Other product and company names mentioned herein are trademarks or trade names of their respective companies. For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software, the patents.txt file on your CD, or ni.com/patents.