• Use the inverter under the conditions of overvoltage category II (usable regardless of the earth (ground) condition of the power supply), overvoltage
category III (usable with the earthed-neutral system power supply, 400 V class only) and pollution degree 2 or lower specified in IEC60664. An insulating
transformer needs to be installed in the input side of the FR-F820 series inverters.
• To use the inverter of FR-F820-01250(30K) or higher and FR-F840-00770(37K) or higher (IP00) under the conditions of pollution degree 2, install it in the
enclosure of IP 2X or higher.
• To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
• To use the inverter of FR-F820-00930(22K) or lower and FR-F840-00620(30K) or lower (IP20) outside of an enclosure in the environment of pollution
degree 2, fix a fan cover with fan cover fixing screws enclosed.
• On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C.
• The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30VDC, 0.3A. (Relay output has basic isolation from the
inverter internal circuit.)
• Control circuit terminals on
page 5
• Environment (For the detail, refer to
During Operation
LD rating: -10 to +50°C
Surrounding air temperature
SLD rating: -10 to +40°C
Ambient humidity
95% RH or less
Maximum altitude
2500 m
 Wiring protection
Class T, Class J, Class CC, or Class L fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided.
For the FR-F820 series, Class T, Class J, or Class CC fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided.
FR-F820-[]
Rated fuse voltage (V)
Without power factor
Fuse Maximum
improving reactor
allowable rating
With power factor
(A)

improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-F820-[]
Rated fuse voltage (V)
Without power factor
Fuse Maximum
improving reactor
allowable rating
With power factor
(A)

improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-F840-[]
Rated fuse voltage (V)
Without power factor
Fuse Maximum
improving reactor
allowable rating
With power factor
(A)

improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-F840-[]
Rated fuse voltage (V)
Without power factor
Fuse Maximum
improving reactor
allowable rating
With power factor
(A)

improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)


Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
 Short circuit ratings
• 200 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 240 V Maximum.
• 400 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 500 V Maximum.
Fan cover
fixing screw
Fan cover
Fan
FR-F820-00105(2.2K) to 00250(5.5K)
FR-F840-00083(3.7K), 00126(5.5K)
are safely isolated from the main circuit.
page
3.)
In Storage
-20 to +65°C
95% RH or less
2500 m
00046
00077
00105
00167
00250
(0.75K)
(1.5K)
(2.2K)
(3.7K)
(5.5K)
240 V or more
15
20
30
40
60
15
20
20
30
50
15
15
25
40
60
00930
01250
01540
01870
02330
(22K)
(30K)
(37K)
(45K)
(55K)
240 V or more
225
300
350
400
500
200
250
300
350
400
225
300
350
450
500
00023
00038
00052
00083
00126
(0.75K)
(1.5K)
(2.2K)
(3.7K)
(5.5K)
500 V or more
6
10
15
20
30
6
10
10
15
25
15
15
15
20
30
00930
01160
01800
02160
02600
(45K)
(55K)
(75K)
(90K)
(110K)
500 V or more
200
250
175
200
250
300
350
225
250
450
450
500
Fan cover
fixing screw
Fan cover
Fan
FR-F820-00340(7.5K) to 00930(22K)
FR-F840-00170(7.5K) to 00620(30K)
During Transportation
-20 to +65°C
95% RH or less
10000 m
00340
00490
00630
00770
(7.5K)
(11K)
(15K)
(18.5K)
80
150
175
200
70
125
150
200
80
110
150
190
03160
03800
04750
(75K)
(90K)
(110K)
500
600
700
700
900
1000
00170
00250
00310
00380
00470
(7.5K)
(11K)
(15K)
(18.5K)
(22K)
40
70
80
90
110
35
60
70
90
100
40
60
70
90
100
03250
03610
04320
04810
05470
(132K)
(160K)
(185K)
(220K)
(250K)
400
500
600
700
800
00620
00770
(30K)
(37K)
150
175
125
150
150
175
06100
06830
(280K)
(315K)
900
1000
29
Appendix