Thermistor Calibration In Controller; Fan Speed At Cooling Thermo-Off - Hitachi PC-ARFG-E Installation & Operation Manual

Wired remote controller
Hide thumbs Also See for PC-ARFG-E:
Table of Contents

Advertisement

SERVICE & INSTALLATION MENU

6.1.5 Thermistor Calibration in Controller

This function is used to calibrate the temperature sensor
embedded into the wired remote controller
The temperature compensation value can be set in 0.5°C
increments within a range of ±3.5°C.
1 Select "Installation Menu" on the Service & Installation
screen and press "OK".
2 Select "Thermistor Calibration in Controller" setting and
press "OK".
3 Select the temperature compensation value by pressing " ",
" " and press "OK".
4 Press " " or " " to select "OK ". Press "OK", the screen
returns to the "Installation Menu".
61
PMML0565 rev.1 - 04/2022

6.1.6 Fan Speed at Cooling Thermo-OFF

This function is used to set the fan speed of the indoor unit at
Cooling Thermo-OFF.
1 Select "Fan Speed at Cooling Thermo-OFF"on the
"Installation Menu" screen and press "OK".
2 Press " ", " ", " " or " " to select the indoor unit. Press
If there is only one indoor unit connected to the wired remote
controller, this screen is not displayed (the Step3 screen is
shown).
3 If " " or " " is pressed, the fan speed is selected in the
following order: "Unavailable" ↔ "Low" ↔ "BREEZE". Select
the fan speed and press "OK" to confirm the setting.
4 Press " " to return to the "Installation Menu" screen.
?
N O T E
This menu is a shortcut to set the optional function setting Eb.
This menu is not allowing to stop the fan during Cooling Thermo OFF.
Refer to the optional function parameters Cd for such option.