SERVICE & INSTALLATION MENU
Continue from previous page
Abnormality counter
17
Times of abnormality
18
Times of power failure
Times of abnormal transmitting
19
(remote controller-outdoor unit)
20
Times of inverter tripping
Control Information Display
21
Control information
Pressure / Frequency
22
Discharge Pressure
23
Inlet pressure
24
Control Information
25
Operating frequency (Hz)
Indoor unit capacity / Model / System number display
26
Indoor unit capacity
27
Outdoor unit model
28
System number
29
System number
Continue to next page
Code
Indoor unit capacity number
06
22
08
28
10
36
11
40
13
45
14
50
16
56
18
63
84
PMML0565 rev.1 - 04/2022
E1
01
E2
00
E3
00
E4
00
F1
00
H1
18
For units without high pressure sensor, the value for H2 is a control
H2
04
information. Unit is (×0.1MPa). Value for unit A is shown for multi-type
units.
H3
44
Operating frequency of the compressor is shown. (Max. number for this
H4
44
item is 255) For units without inverter compressor, the value for H4 is a
control information.
J1
08
J2
F.01
J3
01
J4
00
Equivalent horse power
0.8
1.0
1.3
1.5
1.8
2.0
2.3
2.5
This number is incremented when transmission error occurs between
Wired Remote Controller and Indoor units and the error remains for 3
minutes or longer.
The maximum count is 99. (99 is indicated for 99 or more)
For units without high pressure sensor, the value for H1 is a control
information. Unit is (×0.1MPa). Value for unit A is shown for multi-type
units.
Internal information of Wired Remote Controller is shown.
Indoor unit capacity code
Model code
Indication
H
P
F
C
E
b
L
*1: n indicates the quantity of the indoor units that are connected to the
system (n=01-16). "E.00" is shown if communication error is occurred
between indoor units and outdoor units.
*2: For former outdoor units (models before 2010 April), "P" is shown.
J3:01-64 (Set the shipping status of RSW5 to 01 and decimal
representation)
J4:00-3F(Set the shipping status of RSW5 to 00 and hexadecimal
representation)
Code
Indoor unit capacity number
20
71
22
80
26
90
32
112
40
140
48
160
64
200 - 224
80
280
Model
Heat pump
Inverter
Multi (SET-FREE)
Cooling only
Other
IVX, individual operation
KPI
Equivalent horse power
2.8
3.0
3.3
4.0
5.0
6.0
7.5 - 8.0
10.0