Power Up Setting; Setback Trigger Unit - Hitachi PC-ARFG-E Installation & Operation Manual

Wired remote controller
Hide thumbs Also See for PC-ARFG-E:
Table of Contents

Advertisement

SERVICE & INSTALLATION MENU
3 Select "Yes" and press "OK" to confirm the configuration.
4 When "Cancel" is selected, the screen returns to the
"Elevating Grille Setting" menu.

6.1.16 Power Up Setting

This function is used to set the maximum compressor frequency
and the target compressor frequency higher than usual. Power
up operation is performed after starting operation in the selected
operation mode (COOL only - HEAT ONLY - COOL+HEAT). This
function is available only for the compatible H-LINK 2 outdoor
units.
Please check the relevant technical information of the unit in
order to know if is compatible for this function.
1 Select "Power Up Setting"on the "Installation Menu" screen
and press "OK".
2 If " " or " " is pressed, the settings are selected in the
following order: "OFF" ↔ "COOL" ↔ "HEAT" ↔ "Cool +
Heat" Select the setting and press "OK" to confirm the
setting.
3 Press " " to return to the Installation Menu.
69
PMML0565 rev.1 - 04/2022

6.1.17 Setback Trigger Unit

The setback trigger unit can be set from the Installation Menu.
1 Select the indoor unit by pressing " ", " ", " ", or " " and
press "OK" to display the confirmation screen.
2 Select "Yes" and press "OK" to confirm the setting. Then,
please wait a moment until the screen shows "Completed" or
"Setting Disabled".
If "Cancel" is selected, the screen returns to the Setback
Trigger Unit screen.

Advertisement

Table of Contents
loading

Table of Contents