Oltc Monitor Commissioning - GE Kelman DGA 900 Plus Installation & Commissioning Manual

Transformer monitoring system
Table of Contents

Advertisement

Cooling Condition
The product supports up to four cooling banks. Each bank can be independently set to
zero, and the operational time and switching can also be reset.
Note:
After installation, it is advisable to reset all the counters to zero
Note:
Before resetting the counters, ensure that the internal time and date are
correct. (The internal time can be found on the dashboard home page).
Click Reset to Zero to reset the listed parameters to hold a value of zero.

10.3 OLTC Monitor Commissioning

DGA 900 Plus products with an OLTC card enabled must undergo OLTC commissioning
to ensure optimal and correct use of the following models:
OLTC Tap Position Tracking
OLTC Motor Torque
OLTC Temperature
Commissioning determines the following:
Mapping for mechanical position number to analogue input current
Generation of group calculation parameters
Limits for OLTC motor torque model alarms
The models require custom parameters unique to each tap changer. These can be found
in the customer-specific 'Models Configurator' spreadsheet (available from the GE
Service Team). OLTC commissioning requires the A14 (tap position) and A17 (motor
torque) inputs.
OLTC monitor installation and commissioning must be performed on a non-
energised transformer.
After installing the OLTC Motor Power Converter, the OLTC Tap Position
and OLTC Torque models must be left disabled (refer to 'Section 6.4: Models
Activation and Status' in the 'MA-040 – DGA 900 Plus – Operator Guide')
until commissioning is successfully completed.
Table 10-1lists the OLTC software requirements for commissioning.
Table 10-1: OLTC software requirements
Laptop or
computer
equipped
with the
following
software:
Table 10-2 lists the OLTC commissioning files.
MA-041 – DGA 900 Plus - Installation & Commissioning Manual - Rev 1.1
OLTC Software Requirement
Perception Desktop
Microsoft Excel
Text editor e.g. Notepad (available as default in Windows) or Notepad++
Latest DGA 900 Plus firmware (installed on the product)
4-Mar-22
Page 73 of 99

Hide quick links:

Advertisement

Table of Contents
loading