Figure 9-44: Save As "AdaptorOnly"
9.8.2.2.5 Adaptor Installed
Connect the Bushing Adaptor to the bushing tapping point as outlined in Section 9.4
Bushing Adaptors.
Click the 'Start/Stop Measurement' button
Figure 9-43.
Select File > Save As and type the filename AdaptorInstalled as shown in Figure
9-45.
Figure 9-45: Save As "AdaptorInstalled"
Click the 'Show Previous' button
on the graph (the previous scan as well as the latest scan) as shown in Figure 9-46.
The internal pin of the Bushing Adaptor must make electrical contact with the bushing
tapping point for a phase change to occur as demonstrated in the example shown in
MA-041 – DGA 900 Plus - Installation & Commissioning Manual - Rev 1.1
to start a measurement as shown in
to compare the waveforms of both sets of data