GE Kelman DGA 900 Plus Installation & Commissioning Manual page 56

Transformer monitoring system
Table of Contents

Advertisement

Figure 9-28: AntScope New measurement – Configure > AA-170 Analyzer
In Windows File Explorer, create a new folder for the installation of each Bushing
Adaptor phase.
9.8.2.2 RigExpert Tests
9.8.2.2.1 Open Circuit Test
Place the coaxial cable so that during the calibration and the subsequent
measurements minimal movement of the cable will occur. Leave the clips
unconnected, i.e. open circuit, as shown in Figure 9-29.
Figure 9-29: Open calibration
Select Measurement > Range to configure the resolution and scan range. Select
Limits and set the limits from 0 to 50,000 kHz. In the Resolution field, type 100
points and click OK as shown in Figure 9-30. A measurement will be triggered.
MA-041 – DGA 900 Plus - Installation & Commissioning Manual - Rev 1.1
4-Mar-22
Page 56 of 99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents