Hydraulic Balancing; Special Points Related To Cooling; Expansion Vessel - Panasonic Aquarea WH-ADC0309J3E5 Planning And Installation Manual

Air-to-water heat pumps
Hide thumbs Also See for Aquarea WH-ADC0309J3E5:
Table of Contents

Advertisement

Consideration of the nominal flow rate
For efficient heat generation, heat pumps use a temperature difference of about 5 K between the
supply and return water flow. This distinguishes them from heat sources with boilers, which can
work without any problem with a temperature difference of about 10 or 20 K between the supply
and return water flow. A consequence of the small temperature difference in heat pumps is that the
flow rate of heat pumps, which is needed to transport the heat within the circuit, must be higher
than for heat sources with boilers with the same thermal output. The nominal flow rate and the
resulting resistance of the pipe network must therefore be given special attention at the time of
design.
Consideration of the nominal pipe width
The pressure drop in the pipe rises exponentially with the flow rate. This means that doubling the
flow rate causes the pressure drop to increase by a factor of 4. The decisive aspect for this is the
flow speed in the pipe that depends on the flow rate and inner diameter.
As an alternative to a pipe network calculation, a nomogram can be used to determine the pressure
drop across pipe segments. Recommendations for designing the main distribution circuit are:
● The flow speed should be in the range of 0.3 to max. 1.5 m/s.
● The pressure drop per metre should be about 0.1 kPa/m.
Based on these criteria, the required nominal pipe width can be read off from the copper tube
nomogram. To determine the pipe network resistance of a complete pipe run, first, the pressure
drop per metre must be multiplied by the length of each pipe segment, and then the pressure drops
of all segments must be summed up. The total resistance of a complete pipe run is obtained as the
total pressure drop of all pipe segments multiplied by a lump sum supplement factor of 1.5.
!
IMPORTANT
The total of the individual resistances of all components of the pipe network must not exceed the
pump discharge head for the nominal flow rate. If the pipe network resistance is too high, the unit's
integrated water circulation pump cannot achieve the nominal flow rate. The heat pump control
functions will register a shortfall of the minimum circulation quantity and throw an alarm.

5.3.3 Hydraulic balancing

Hydraulic balancing of the heat transfer system is the process of optimising the set flow rates for
several pipe segments through regulating valves. This prevents individual building areas from being
excessively overheated, while other areas with a lower flow rate remain cold. Hydraulic balancing
therefore raises the living comfort and is, at the same time, also a requirement for efficient
operation of the air-to-water heat pump. Therefore, hydraulic balancing is also a prerequisite for the
financial promotion of heat pumps.

5.3.4 Special points related to cooling

Hydraulically, a heat pump system with cooling mode does not differ from a heating-only system.
However, to correctly determine the total annual amount of heat and cold delivered by the heat
pump, which is needed to calculate the seasonal coefficient of performance, it is necessary to use
energy meters which record the amount of heat as well as the amount of cold.

5.3.5 Expansion vessel

The Aquarea heat pumps have an integral expansion vessel with a model-specific volume of 6 or
10 litres (see table) and an initial pressure of 1 bar.
The volume of the expansion vessel is adequate for heating systems whose total water quantity
and its static height (difference of the highest point of the system to the expansion vessel) must not
exceed defined limits.
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Planning
5
113

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents