Caution Signs - ABB Relion 670 Series Commissioning Manual

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 2
Safety information
2.3

Caution signs

20
Always connect the IED to protective earth, regardless of the operating conditions.
This also applies to special occasions such as bench testing, demonstrations and
off-site configuration. This is class 1 equipment that shall be earthed.
Never disconnect the secondary connection of current transformer circuit without
short-circuiting the transformer's secondary winding. Operating a current transformer
with the secondary winding open will cause a massive potential build-up that may
damage the transformer and may cause injuries to humans.
Never remove any screw from a powered IED or from a IED connected to powered
circuitry. Potentially lethal voltages and currents are present.
Take adequate measures to protect the eyes. Never look into the laser beam.
The IED with accessories should be mounted in a cubicle in a restricted access area
within a power station, substation or industrial or retail environment.
Whenever changes are made in the IED, measures should be taken to avoid
inadvertent tripping.
The IED contains components which are sensitive to electrostatic discharge. ESD
precautions shall always be observed prior to touching components.
Always transport PCBs (modules) using certified conductive bags.
Do not connect live wires to the IED. Internal circuitry may be damaged
Always use a conductive wrist strap connected to protective earth when replacing
modules. Electrostatic discharge (ESD) may damage the module and IED circuitry.
Take care to avoid electrical shock during installation and commissioning.
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 511 403-UEN Rev. K
M2369-2 v3
M2367-2 v1
M2372-2 v1
SEMOD168311-3 v1
GUID-11CCF92B-E9E7-409C-84D0-DFDEA1DCBE85 v2
IP1503-1 v1
GUID-5D1412B8-8F9D-4D39-B6D1-60FB35797FD0 v3
GUID-F2A7BD77-80FB-48F0-AAE5-BE73DE520CC2 v1
M2695-2 v2
M2696-2 v1
M2697-2 v2
M2698-2 v2
Bay control REC670
Commissioning manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents