ABB Relion 670 Series Commissioning Manual page 195

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 403-UEN Rev. K
11.13.1.1
Function revision history
Document
revision
A
B
C
D
E
F
G
H
11.13.1.2
Testing the gas medium supervision for pressure alarm and pressure
lockout conditions
1.
Connect the binary inputs to consider gas pressure and gas density to initiate the alarms.
2.
Activate the binary input SENPRESQ.
3.
Consider the analogue pressure input SENPRES and set SENPRES to a value lower than
PresAlmLimit or activate binary input signal SENPRESALM, check that outputs PRESALM and
ALARM are activated after a set time delay of tPressureAlarm.
4.
Gas pressure lockout input SETPLO can be used to set PRESLO.
5.
Ensure that binary input SENPRESQ is activated and reduce further the pressure level input
below PresLOLimit or activate the binary input signal SENPRESLO, check that PRESLO signal
appears after a set time delay of tPressureLO.
6.
Activate BLOCK binary input and check that the outputs PRESALM, PRESLO, ALARM and
LOCKOUT disappears.
7.
Reset the BLOCK binary input.
8.
Ensure that pressure lockout condition exists and then activate the reset lockout input
RESETLO and check that the outputs PRESLO and LOCKOUT reset.
11.13.1.3
Testing the gas medium supervision for temperature alarm and
temperature lockout conditions
1.
Activate the binary input SENTEMPQ.
2.
Consider the analogue temperature input SENTEMP and set SENTEMP to a value higher than
TempAlarmLimit, check that outputs TEMPALM and ALARM are activated after a set time delay
of tTempAlarm.
3.
Temperature lockout input SETTLO can be used to set TEMPLO signal.
4.
Ensure that binary input SENTEMPQ is activated and increase further the temperature input
above TempLOLimit, check that the outputs TEMPLO and LOCKOUT appear after a set time
delay of tTempLockOut.
5.
Activate BLOCK binary input and check that the outputs TEMPALM, TEMPLO, ALARM and
LOCKOUT disappear.
6.
Reset the BLOCK binary input.
7.
Ensure that temperature lockout condition exists and then activate the reset lockout input
RESETLO and check that the outputs TEMPLO and LOCKOUT reset.
Bay control REC670
Commissioning manual
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
2.2.4
-
2.2.4
Binary quality inputs SENPRESQ and SENTEMPQ have been added for pressure and
temperature sensor signals in order to control alarm and lockout signals. Whenever there
is no sensor, the quality of the binary input will be low. If sensor quality is low, then
lockout and alarm signals will get reset.
2.2.5
-
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 11
Testing functionality by secondary injection
GUID-7F31EFA5-F8D8-4D8D-85DA-3418F70ABE94 v2
GUID-768DAAC8-F89D-4401-B86D-9B26FD7224F6 v5
GUID-EC145626-90B0-45A2-AD58-CB8BF203FE16 v3
189

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents