Calibrate The Channels - GE Bently Nevada 3300/25 Operation Manual

Dual accelerometer input monitor
Table of Contents

Advertisement

3300/25 Dual Accelerometer Input Monitor Operation Manual

15.3 Calibrate the Channels

(Repeat for channels A and B)
1.
Measure the proportional signal output at TP39 (BPPLA) for Channel A and TP40
(BPPLB) for Channel B. The testpoint locations are shown in the figure below. The
voltages at these testpoints should match the voltages listed in the following table.
TRIP MULTIPLY OPTION
2.
Adjust potentiometer GA (gain adjust A) for Channel A, and GB for Channel B, to
the appropriate Proportional Output (Vdc) shown above.
40
PROPORTIONAL OUTPUT (Vdc)
NONE
2X
3X
+5.000
+2.500
+1.670