12 EN - Quick installation and start-up guide

Input power cable

4. Prepare the ends of the cable as illustrated in the figure.
Note: The bare shield will be grounded 360°. Mark the pigtail made from the shield as a PE
conductor with yellow-and-green color
EN
HI
5. Connect the input power cable as follows:
Connect the twisted shield of the cable to the grounding terminal (5a).
Connect the phase conductors of the cable to the L1, L2 and L3 terminals.
5a
Tighten the screws to the torque given below:
Frame size
6. Connect the braking resistor cable as the motor cable. See step 3.
7. Ground the shield 360° (6a).
8. Connect the twisted shield to the grounding terminal (6b) and the conductors to the
UDC+/R+ and R- terminals (6c).
PE
PE
5b
L1, L2, L3
0.5...0.6
R0...R1
N·m
lbf·ft
0.4
R2
N·m
lbf·ft
1.2...1.5
0.9...1.1