ABB ACS560 Quick Installation And Start-Up Manual page 113

Standard control program
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Code
Warning/Aux code
(hex)
(aux code visible
only on assistant
control panel and
drive composer)
A5F2
Overtemperature hw
A682
Flash erase speed
A684
Power fail saving
A6A4
Motor nominal value
1 – Slip frequency is too small
2 – Synchronous and nominal speeds differ too
much
3 – Nominal speed is higher than synchronous
speed with 1 pole pair
4 – Nominal current is outside limits
A6A5
No motor data
A6A6
Voltage category un-
selected
A6A7
System time not set
A6B0
User lock is open
A6B1
User pass code not
confirmed
A6D1
FBA A parameter
conflict
A6E5
AI parametrization
A6E6
ULC configuration
0000
0002
0003
Cause
Excessive hardware temperat-
ure.
Flash erase speed exceeded.
Power fail saving warning.
The motor parameters are set
incorrectly. The drive is not di-
mensioned correctly.
5 – Nominal voltage is outside limits
6 – Nominal power is higher than apparent
power.
7 – Nominal power not consistent with nominal
speed and torque
Parameters in group 99 are not
set.
Voltage category is not defined.
System time is not set.
The user lock is open, ie. user
lock configuration parameters
96.100...96.102 are visible.
New pass code is entered in
parameter 96.100 and not con-
firmed in 96.101.
PLC requested functionality is
not activated.
Current/voltage hardware setting
of an analog input does not cor-
respond to parameter settings.
User load curve configuration
error.
Speed points inconsistent.
Underload point above overload
point.
Overload point below underload
point.
Diagnostics 113
What to do
Contact your local ABB representative.
Avoid forcing unnecessary parameter saves
by parameter 96.07 Parameter save manu-
ally or cyclic parameter writes (such as user
logger triggering through parameters).Check
the auxiliary code (format XYYY YZZZ). "X"
specifies the source of warning (1: generic
flash erase supervision). "ZZZ" specifies the
flash subsector number that generated the
warning.
Contact your local ABB representative.
Check the settings of motor configuration in
parameter groups 98 and 99 and check if
drive is sized correctly for the motor.
Set the required parameters in group 99.
Set voltage category in parameter 95.01
Supply voltage.
Close the user lock by entering an invalid
pass code in parameter 96.02 Pass code.
Confirm the new pass code by entering the
same code in 96.101.
Check PLC programming.
Adjust the hardware setting on the drive
control unit or the parameter 12.15/12.25.
Check the auxiliary code (format XXXX
ZZZZ). "ZZZZ" indicates the problem (see
actions for each code below).
Check that each speed point (parameters
37.11...37.15) has a higher value than the
previous point.
Check that each overload point
(37.31...37.35) has a higher value than the
corresponding underload point
(37.21...37.25).
EN
HI