Mitsubishi Electric AG-150A Installation Manual page 11

Air-conditioner control system
Hide thumbs Also See for AG-150A:

Advertisement

(6) Install the power supply unit (PAC-SC51KUA; sold separately) inside the Mounting attachment A type with the four M4 screws
(supplied).
(Refer to section 1.(6).)
(7) Connect the cables to the power supply unit (PAC-SC51KUA).
Refer to the PAC-SC51KUA Installation Manual for details.
(8) Remove the AG-150A surface cover.
(9) Connect the wiring from the power supply unit to the centralized controller.
(Refer to section 1.(9).)
(10) If the AG-150A is not always connected to the LAN, connect the supplied LAN link-up cable to the LAN connector.
(* If the AG-150A is always connected to the LAN, connect the LAN cable (field supplied) via a HUB and the LAN link-up
cable is not required.)
(11) To use the external I/O, connect the external I/O cable (PAC-YG10HA; sold separately) to CN5 on the AG-150A.
(12) Install the centralized controller inside the Mounting attachment A type with the four M4 screws (supplied).
If the LAN link-up cable is used, place it inside the Mounting attachment A type.
(Refer to section 1.(13).)
(13) Attach the cover on the AG-150A.
(14) Attach the power supply unit cover with the two screws.
(Refer to section 1.(15).)
7 LAN link-up cable
The LAN link-up cable is used for maintenance purpose when the AG-150A is not always connected to the LAN.
If the AG-150A is not always connected to the LAN, connect a LAN cable to the LAN link-up cable to upgrade the AG-150A software
as necessary.
LAN link-up cable
Remove the cover of Mounting attachment A type to use the LAN link-up cable.
Refer to section 1.(1) in 6. Installation for how to remove the cover.
LAN cable
- 11 -