Mount of drawout handle

The drawout handle can be mounted on any of the left and right sides of the cradle.
¡Mounting on the left side
Handle holder
Cradle
Fig. 8-1

Attach the Inter-phase Barrier

Insert in the slot on the breaker.
<Fixed type>
Fig. 8-4
E − 8
¡Mounting on the right side
Drawout handle
Nut M5
Fig. 8-2
Mtg. Screw M5 ✕ 12
2.8 ~ 3.6 N·m
<Drawout type>
Fig. 8-5
Note: The drawout handle cannot be mounted
on the left side of the cradle when the
cradle is provided with a mechanical
inter lock (MI) or a door inter lock (DI).
Mount the handle at an appropriate
position in the panel.
Mechanical interlock (MI)
or
door interlock (DI)
Fig. 8-3