Characteristics Setting Of Type Wb Relay - Mitsubishi Electric AE-SW Series Instruction Manual

Low-voltage air circuit breakers
Hide thumbs Also See for AE-SW Series:
Table of Contents

Advertisement

Characteristics setting of type WB relay

1
Note: The figure include MCR function.
Table 24
No.
Setting item
Mark
Current setting
Ir
1
AE630-SW~AE1600-SW
AE2000-SW~AE3200-SW, AE4000-SW
INST/MCR
AE2000-SWA, AE4000-SWA
Ii
6
pick-up current
AE5000-SW
AE6300-SW
Pre-alarm current
Ip
7
8
Pre-alarm time
Tp
The table shows data obtained on the breakers provided with MCR (optional). For breakers without MCR, the setting position for MCR is not provided.
Relation of setting dial
Ir
In (CT rating)
Ii
Ip
Ip2 (Page 26)
Load current LED (60, 80, 100, OVER)
Ig (Page 25)
E − 24
7
8
6
7
Adjustable setting range
0.5 ~ 1.0 (0.05step) ✕ In (CT rating)
16-12-10-8-6-4-2-2-4-6-8-10-12-16
(INST)
12-10-8-6-4-2-2-4-6-8-10-12
(INST)
10-8-6-4-2-2-4-6-8-10
(INST)
Ir ✕ 0.68 ~ 1.0 (0.04step)-OVER
75s at Ir ✕ 2 (after 75s, PAL contact output turns on.)
Pre-alarm
current: Ip
Pre-alarm
time: Tp
6
INST pick-up
current: Ii
Current (%)
✕ Ir
(MCR)
WB1
✕ Ir
(MCR)
WB2
✕ Ir
(MCR)
WB3
Max. setting of
let-through current
Max. setting of
external OCR
Up to Icw
Up to Icw
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
Factory default
Accuracy
value
1.0
WB1···16 (INST)
±15%
WB2···12 (INST)
WB3···10 (INST)
±10%
OVER
±20%

Hide quick links: