Measurement Items (Detail); Setting Items (Detail) - Mitsubishi Electric AE630-SW Instruction Manual

Low-voltage air circuit breakers type ae, cc-link interface unit bif-md
Hide thumbs Also See for AE630-SW:
Table of Contents

Advertisement

5.2 Measurement items (detail)

The detailed specifications for measurement items are shown in table 5.2.
Detailed specifications for measurement items
Table 5.2:
Items (Accuracy)
5)
Load current (±2.5%
)
2), 4)
5)
Earth leakage
(±15%
)
line
Voltage
4)
(±2.5%
5)
)
phase
active
Power
4)
(±2.5%
5)
)
reactive
apparent
3)
4), 7)
5)
Power factor
(±5.0%
)
active
4)
6)
Energy
(±2.5%
)
reactive
rms
Harmonic current
5)
(±2.5%
)
distortion/ratio [0.1%]
6)
Frequency (±2.5%
)
6)
Trip current (±20%
)
■1): "○", "×" and "△" represents "available", "not available" and "available on phase 1 to phase 3", respectively.
■2): Including the accuracy of ZCT.
■3): When using at 3φ3W system, the apparent power is calculated by (√3/2)×(I1×V12 + I3×V23).
Therefore, the accuracy may not be ensured in the unbalanced circuit.
■4): Rated voltage of measurement is 440V. Rated power and energy of measurement is √3×In×440V.
Rated earth leakage current of measurement is IΔn_max (=10A). Rated power factor is 90 degrees.
■5): Accuracy and cut off are defined as percentage of rated value.
■6): Accuracy is defined as percentage of true value.
■7): Power factor is measured for only fundamental wave. A waveform distortion is not included for power factor calculation.

5.3 Setting items (detail)

The detailed specifications for setting items are shown in table 5.3.
Table 5.3: Detailed specifications for setting items
Items
Year
Month
Day
Date and time
Hour
Minute
Second
Load current
Demand time
Leakage current
Power
Alarm holding method
Iep
EPAL
Tep
■1): When Iep is set to 0, the EPAL function is disabled (*default setting).
■2): Iep must be set to IΔn or less.
Unit
[0.1A] (*In< 500A)
[A] (*In≥ 500A)
[mA]
[V]
[V]
[0.1kW] (*In< 1000A)
[kW] (*In≥ 1000A)
[0.1kvar] (*In< 1000A)
[kvar] (*In≥ 1000A)
[0.1kVA] (*In< 1000A)
[kVA] (*In≥ 1000A)
[0.1%]
[kWh]
[kvarh]
[0.1A] (*In< 500A)
[A] (*In≥ 500A)
[Hz]
[A] (*cause=LTD/STD/INST/GFR) 0 to 20×In [A]
[mA] (*cause=ER)
Setting range
00(2000) to 99(2099)
01 to 12
01 to 31
00 to 23
00 to 59
00 to 59
0s to 50s (*step: 10s)/
1min to 15min (*step: 1min)/
20min/30min
Auto reset/Self-holding
0
1)
/500mA/600mA/700mA/.../IΔn
100ms/200ms/.../3000ms (*step: 100ms)
E-21
Measurement range
0 to 2×In [A]
0 to 2×IΔn_max [A]
0 to 725 [V]
0 to 420 [V]
-√3×(2×In[A])×725[V]
to +√3× ( 2 × In [ A ] ) ×725
[V]
-√3×(2×In[A])×725[V]
to +√3× ( 2 × In [ A ] ) ×725
[V]
0 to +√3×(2×In[A])×725[V]
-50[%] to 100[%] to +50[%]
0 to 99999999 [kWh]
0 to 99999999 [kvarh]
0 to 2×In [A]
0 to 200 [%]
45 to 65 [Hz]
0 to 2×IΔn_max [A]
Setting for shipment
04(2004)
01
01
00
00
00
2min
2min
2min
Auto reset
2)
(*step: 100mA) 0(=OFF)
3000ms
1)
Phase-Wire
Cut off
3φ3W 3φ4W
5)
2.0%
5)
3.0%
10V
×
10V
2.0%
5)
2.0%
5)
2.0%
5)
-
5)
0.4%
5)
0.4%
5)
2.0%
-
-
-