Huawei FusionModule500 Quick Manual page 20

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

3.11
Commissioning Cabinet Electronic Clasp Locks
1. Set device addresses for cabinet electronic clasp locks.
A cabinet electronic clasp lock is installed at the front and rear doors of the cabinet
respectively. The address for the cabinet electronic clasp lock on the front door is an odd
number, and that for the cabinet electronic clasp lock on the rear door is an even number.
Set a device address for a cabinet electronic clasp lock by operating the toggle switch on the
cabinet electronic clasp lock. Toggle switches 1 to 6 specify the device address in binary
mode. ON indicates 1, and OFF indicates 0.
Toggle
Address
Switch 1
1
ON
2
OFF
2. Add the cabinet electronic clasp locks.
a. Log in to the ECC800-Pro WebUI as an administrator.
b. Create a cabinet view in Smart Module View on the home page.
c. Add a cabinet electronic clasp lock.
3. Commission the cabinet electronic clasp locks.
3.12
Commissioning Event Notification
1. Choose System Settings > Event Notification.
2. Set outbox parameters.
3. Add an email address for receiving emails.
4. Add a mobile number for receiving event notifications.
5. Set the alarm notification delay time and add alarm notification parameters.
6. Click Confirm. In the re-authentication dialog box, enter Login password and click Submit.
3.13
Commissioning Linkage Control
Unlocking the Cabinet Electronic Clasp Lock When a Fire Alarm Is Generated
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose System Settings > Linkage Control.
3. Ensure that Enable linkage control function is set to Yes.
4. On the Linkage Group tab page, set Link fire control with clasp lock open to on.
5. Modify the AI/DI_3 signal name.
6. Enable the AI/DI device.
Unlocking the Cabinet Electronic Clasp Lock When a Smoke Alarm Is Generated
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose System Settings > Linkage Control.
3. Ensure that Enable linkage control function is set to Yes.
4. On the Linkage Group tab page, set Link smoke alarm with clasp lock open to on.
5. Modify the AI/DI_1 signal name.
6. Enable the AI/DI device.
Toggle
Toggle
Switch 2
Switch 3
OFF
OFF
ON
OFF
19
Toggle
Toggle
Switch 4
Switch 5
OFF
OFF
OFF
OFF
Toggle
Switch 6
OFF