2
Power-On Commissioning for the Cooling System
2.1
Powering on Devices
1. Switch on the smart cooling
product circuit breaker in the
upstream PDB.
2. Commission the system after
the electric heating belt of
the crankcase has been
preheated for 12 hours.
2.2
Initial Configuration
1. Add the NetCol5000-A0031.
2. Set the running parameters and control parameters for the NetCol5000-A0031 on the
WebUI.
On the Running Parameters tab page, you are advised to set Temperature setpoint to 23 ° C,
Humidity setpoint to 50% RH, Control mode to Cold aisle average value control, and Cold
aisle T/H sensor fault enable and Hot aisle T/H sensor fault enable to Enable.
2.3
Commissioning Procedure
Before commissioning, ensure that the smart cooling product has been powered on.
Before starting the compressor, ensure that the crankcase heating belt has warmed up for
more than 12 hours.
1. Log in to the ECC800-Pro WebUI as admin, and choose Monitoring > Cooling >
NetCol5000-A0031 to enter the smart cooling product commissioning page.
2. Choose Controls > Control Information, set Power on/off to ON, and click Submit.
3
Power-On Commissioning for the Management System
3.1
Preparations and WebUI Login
1. Connect a network cable between the PC network port and the WAN_1 port on the ECC800-
Pro.
2. Configure the PC IP address and the WAN_1 IP address in the same network segment.
3. Set LAN parameters.
4. Set Internet Explorer parameters.
5. Log in to the ECC800-Pro WebUI.
Change the password immediately after the first login.
3.2
Preparations and App Login
1. Download and install the FusionModule app from Huawei AppGallery.
Huawei AppGallery installed on the PAD: Log in to the Huawei AppGallery client, search for
FusionModule, and tap Install.
Huawei AppGallery not installed on the PAD:
Method 1: Log in to Huawei AppGallery (https://appgallery.huawei.com/), search for
FusionModule, and tap Install.
Method 2:Log in to the ECC800-Pro WebUI on a PC and scan the QR code to install the app.
Before starting the compressor, ensure that the electric
heating belt of the crankcase has been preheated for
more than 12 hours. Otherwise, the compressor may be
faulty, and Huawei will not be liable for any loss caused
thereby.