Tubing Connections; Port Locations - ABB AV1 Operating Instructions Manual

Actuators & positioners
Hide thumbs Also See for AV1:
Table of Contents

Advertisement

TUBING CONNECTIONS

V IE W W ITH G AG E
B L O C K (AV ?? ?3 ?? ?)
1. Connect the required supply air to connection S (Fig. B-5).
NOTE: Maximum torque for ¼-NPT fittings is 13.6 Nm (10.0 ft-lbs).
G AG E
PO RT S
V IE W W ITH M A N IFO L D
(AV ? ?? 1? ? ? O R
AV ? ?? 2? ?? )
Figure B-5. Port Locations
2. Based on the positioner type, perform one of the following steps
(Fig. B-5):
AV11 and AV15: Connect 20.7 to 103.4-kPa (3.0 to 15.0-psig)
instrument signal to connection I.
AV12 and AV16: Connect 20.7 to 186.2-kPa (3.0 to 27.0-psig)
instrument signal to connection I.
AV2: Connection I is not used and should be plugged. If it is not
plugged, do so at this time.
NOTE: Use liquid or paste pipe sealant to seal the connection. Max-
imum torque for ¼-NPT fittings is 13.6 Nm (10.0 ft-lbs).
3. Connect the output ports 01 and 02 as required to provide the
desired direction of rotation. Figures B-6, B-7,
single acting tubing example, and Figure
tubing example.
NOTE: The piping arrangements shown in Figures B-6, B-7, B-8,
B-9
and
B-10
are general examples and may not reflect the arrange-
ment required for the application.
4. Install
-NPT permanent instrument gages to the gage ports if
1
8
desired or for calibration requirements.
QUICK START
G AG E
PO RT S
C O N D U IT
C O N N EC T IO N
V IE W W ITH O U T
M A N IF O LD
(AV ? ??0? ? ?)
B-8
and
B-9
B-10
shows a double acting
TUBING CONNECTIONS
T 00 80 6 A
show a
B - 5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Av2Sv1121000

Table of Contents