Wiring Type Av1 Positioner; Reverse Acting, Bottom Loaded, Single Acting Tubing Example - ABB AV1 Operating Instructions Manual

Actuators & positioners
Hide thumbs Also See for AV1:
Table of Contents

Advertisement

WIRING TYPE AV1 POSITIONER

HANDJACK
OUTPUT GAGE (O1 PORT)
SIGNAL GAGE
NOTES:
1. RED CAM ROTATES CLOCKWISE WHEN
VIEWED FROM THE FRONT.
2. O2 PORT PLUGGED.
3. STEM MOVES DOWN WITH SIGNAL OR
SUPPLY AIR FAILURE.
Figure 3-13. Reverse Acting, Bottom Loaded,
Single Acting Tubing Example
This section applies to the following positioners:
Type AV1___1__.
Type AV1___2__.
NOTES:
1.
If this is a Type AV1___0__ positioner, no electrical wiring is
required.
2.
If using a twisted shielded pair for signal wiring, ground one
end of the shielded pair at the source. Trim the other end of the
pair, located inside the enclosure, so that bare wires are not
exposed.
1. If equipped with an optional 4 to 20-mA position transmitter
(Type AV1___2__), connect a 24-VDC power supply in series with
the required output load (Table 1-5) to terminals TB1-1 (+) and
TB1-2 (-) (Figs.
3-2
and
information about position transmitters.
2. If equipped with an optional potentiometric position transmitter
(Type AV1___1__), connect a power supply (maximum 35 VDC or
30 VAC) across TB1-1 and TB1-3. Use the signal across TB1-1
and TB1-2 or TB1-2 and TB1-3 for position transmitter feedback.
INSTALLATION
O1
G2
G1
MOTION WITH
INCREASING SIGNAL
3-15). Refer to
Appendix A
WIRING TYPE AV1 POSITIONER
T00891A
for detailed
3 - 13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Av2Sv1121000