PHASE 2 - TRANSMITTER INSTALLATION
Pressure or absolute pressure measurement of a tank
1. Select a tap in the upper part of the tank.
2. Mount the transmitter above the elevation of the process
tap.
3. Connect the + (H) side of the transmitter to the tank.
Pressure or absolute pressure measurement of a liquid in
a pipe
1. Place the tap at the side of the line.
2. Mount the transmitter beside or below the tap for clean
fluids, above the tap for dirty fluids.
3. Connect the + (H) side of the transmitter to the pipe.
- 10 -
gate valve
Dirty fluids
E
gate valve
S
L
H
Clean
fluids