Figure 7-58 RS485

7.24 Setting EMI Parameters

This topic describes how to set parameters, including Read Function Code, Read Mode, Start
Address, and End Address, for the environmental monitoring instrument over the WebUI.
Connect the SmartLogger to an EMI that complies with the standard MODBUS/485 protocol.
The SmartLogger can connect to and manage only one EMI at a time.
The protocol points for EMIs provided by different vendors are varied. Therefore, to obtain
information from an EMI, configure the protocol point on the WebUI of the SmartLogger
properly based on the document delivered by the vendor.
On the Settings tab page, choose Comm. Parameters > EMI and set EMI parameters.
Because of the limited permission, select the user name as Advanced User.
Issue 04 (2013-12-15)
RS485-1 indicates communications port COM1, RS485-2 indicates communications port COM2,
and RS485-3 indicates communications port COM3.
The following baud rates are supported: 4800bps, 9600bps and 19200bps. 9600bps is
recommended.
1 ≤ Start Address ≤ End Address ≤ 247. The address segments for these three ports can overlap.
Set the address scope properly. The broader the scope is, the longer the time is for searching the
devices.
If the EMI model is Handan or Jinzhou Yangguang, select Handan (RYQ-3) or Jinzhou
Yangguang (PC-4) from the drop-down list, as shown in
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 Web User Interface
Figure
7-59.
139