Setting Rs485 Parameters - Huawei SmartLogger1000 User Manual

Hide thumbs Also See for SmartLogger1000:
Table of Contents

Advertisement

SmartLogger1000
User Manual
Figure 7-57 Ethernet
Take the following precautions for setting Ethernet parameters when the SmartLogger
connects to the Internet through a router:
When you change an IP address, a dialog box is displayed asking for your confirmation. After
the IP address is changed, you need to use the new IP address to log in to the system.

7.23 Setting RS485 Parameters

This topic describes how to set RS485 parameters, including Baud Rate, Start Address, and
End Address, over the WebUI.
Correctly set the parameters for the RS485 to ensure the normal communications between the
SmartLogger and the inverters and between the SmartLogger and the environmental
monitoring instrument.
On the Settings tab page, choose Comm. Parameters > RS485 and set Baud Rate, Start
Address, and End Address, as shown in
select the User name as Advanced User.
Issue 04 (2013-12-15)
Set the gateway address to the IP address of the router.
Ensure that the IP address of the SmartLogger is in the same network segment as the
gateway address.
Set the DNS address to the IP address of the router or obtain the DNS address from the
network provider.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
7-58. Because of the limited permission,
7 Web User Interface
138