Modbus Register - Mitsubishi Electric 800 Series Instruction Manual

Rs-485 interface board, rs-485 communication terminals
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

4.5.12

MODBUS register

• System environmental variables
Register
40002
Inverter reset
40003
Parameter clear
40004
All parameter clear
40006
Parameter clear
40007
All parameter clear
40009
Inverter status/control input command
40010
Operation mode/inverter setting
40014
Running frequency (RAM value)
40015
Running frequency (EEPROM value)

Communication parameter settings are not cleared.

At a write, the data is set as the control input command.
At a read, the data is read as the inverter running status.

At a write, the data is set as the operation mode setting.
At a read, the data is read as the operation mode setting.
78
PARAMETER
Definition
Write
Write
Write
Write

Write

Read/write

Read/write

Read/write
Write
Read/write
Any value can be written
Set H965A for the write value.
Set H99AA for the write value.
Set H5A96 for the write value.
Set HAA99 for the write value.
Refer to the following.
Refer to the following.
The display can be changed to the rotations per
minute using Pr.37, Pr.144 and Pr.811. (Refer to the
Instruction Manual (Detailed) of the inverter.)
Remarks