Mitsubishi Electric 800 Series Instruction Manual page 19

Rs-485 interface board, rs-485 communication terminals
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement


The setting value "2 or 12" of Pr.340 is used primarily during communication operation of the inverter via the RS-485 terminals of the
product.
Even if an instantaneous power failure occurs while Pr.57 Restart coasting time ≠ "9999" (with automatic restart after instantaneous
power failure), inverter continues operation at the condition before the instantaneous failure.
When Pr.340 = "1 or 10", if a power failure occurs while the start signal is being input through communication, the start signal is OFF at
power restoration.

The operation mode cannot be directly changed between the PU operation mode and Network operation mode.

Switching between the PU and NET operation modes is available with the
18
PARAMETER
key on the operation panel and the X65 signal.