Operation mode setting

To enable RS-485 communication operation via the RS-485 terminals on the product, select the Network operation
mode for the inverter.
4.1.1

Operation mode switching and communication startup mode (Pr.79, Pr.340)

 Operation mode switching conditions
Operation mode switching conditions
• The inverter is at a stop;
• Both the STF and STR signals are off; and
• The Pr.79 Operation mode selection setting is correct.
(Set with the operation panel of the inverter.)
 Operation mode selection at power ON and at restoration from instantaneous power failure
The operation mode at power ON and at restoration from instantaneous power failure can be selected.
Set a value other than "0" in Pr.340 Communication startup mode selection to select the network operation mode.
After started in network operation mode, parameter write from the network is enabled.
NOTE
• Change of the Pr.340 setting is valid when powering on or resetting the inverter.
• Pr.340 can be changed with the operation panel independently of the operation mode.
• When setting a value other than
• Refer to the Instruction Manual (Detailed) of the inverter for details of Pr.79, Pr.340.
16
PARAMETER
0
in Pr.340, make sure that the initial settings of the inverter are correct.
"
"