• When "Communication Mode" is set to "Multicast" and "Communication Speed" of the master station is set to "1Gbps", the
slave stations with different communication speeds of 1Gbps and 100Mbps cannot be connected on the end side via the
switching hub.
Unicast
No.0 (1Gbps)
TSN HUB
No.1
(100Mbps)
No.0: Master station
No.1, No.2, and No.3: Remote station
■Coexistence of line and star topologies
Line and star topologies can be mixed in the same network configuration.
• When the master station with a communication speed of 1Gbps and a remote station with a communication speed of
100Mbps exist in the structure, set "Communication Period Setting" to "Low-Speed" for the remote station with a
communication speed of 100Mbps.
No.0 (1Gbps)
No.1 (1Gbps)
No.0: Master station
No.1: Local station
No.2, No.3: Remote station
• When the communication speed of the master station is 1Gbps, a connection cannot be established if the total cyclic data
size of all slave stations on the 100Mbps device side exceeds 2K bytes. This includes the devices with a communication
speed of 100Mbps that form a boundary between the communication speed of 1Gbps and 100Mbps.
No.0
No.1
(1Gbps)
(1Gbps)
No.2
(1Gbps)
TSN HUB
No.0: Master station
No.1, No.2: Local station
No.3, No.4, No.5, No.6, No.7, No.8, No.9, and No.10: Remote station
 Set the total cyclic data size within 2K bytes.
No.0 (1Gbps)
No.2 (100Mbps)
No.3
No.1
(1Gbps)
(100Mbps)
No.2 (100Mbps)
Low speed
TSN HUB
No.3
No.4
(1Gbps)
(1Gbps)
Ò
No.5
No.6
(100Mbps)
(100Mbps)
5.1 Structure of Authentication Class B Devices and Ethernet Devices
Multicast
TSN HUB
s)
No.3 (100Mbps)
Low speed
Ò
TSN HUB
No.7
(100Mbps)
5 SYSTEM CONFIGURATION
No.2 (100Mbps)
No.3
(1Gbps)
No.8
(100Mbps)
No.9
(100Mbps)
No.10
(100Mbps)
5
35