Precautions
When a TSN hub is used, check the TSN hub specifications on the CC-Link Partner Association website (www.cc-link.org).

Structure of multicast mode

This mode indicates the availability of connection with a network configuration device when "Communication Mode" under
"Application Settings" is set to "Multicast".
When the communication speed for the master station is set to 1Gbps
This mode indicates the availability of connection with a network configuration device when "Communication Speed" of the
master station is set to "1Gbps".
: Connection available, : Connection available via a switching hub, : Connection not available
S: TSN hub available
H: General-purpose hub available
Device on the master station
side
(A device near the master
station)
Master station
1Gbps
(Authentication
Class B device)
Local station
1Gbps
(Authentication
100Mbps
Class B device)
Remote station
1Gbps
(Authentication
100Mbps
Class B device)
*1 For a slave station with a communication speed of 100Mbps, set "Communication Period Setting" to "Low-Speed".
*2 Slave stations with different communication speeds of 1Gbps and 100Mbps cannot be connected on the end side via the switching hub.
*3 Since cyclic data is sent to the Ethernet device when the Ethernet device is connected to the master station, communication may not be
possible depending on the type of the Ethernet device.
*4 Since cyclic data is sent to an Ethernet device when a local station or remote station is used with an Ethernet device on the end side via
a switching hub, communication may not be possible depending on the type of an Ethernet device.
*5 A connection cannot be established if the total cyclic data size of all slave stations on the 100Mbps device side exceeds 2K bytes. This
includes the devices with a communication speed of 100Mbps that form a boundary between the communication speed of 1Gbps and
100Mbps. ( Page 55 Calculation of the total cyclic data size)
*6 Only one of P1 and P2 of the master station can be used.
*7 For a local station or remote station of a device on the master station side, use a multicast filter supported device. ( Manual for the
device used)
Precautions
When a TSN hub is used, check the TSN hub specifications on the CC-Link Partner Association website (www.cc-link.org).
5 SYSTEM CONFIGURATION
30
5.1 Structure of Authentication Class B Devices and Ethernet Devices
Device on the end side (A device far from the master station)
Local station (Authentication
Class B device)
1Gbps
100Mbps
*2*4
S
*2*4
S
*2*4
S
Remote station (Authentication
Class B device)
1Gbps
100Mbps
*2*4
*1*2*5*6
S
S
*2*4
*1*2*5*7
S
S
*2*4
*1*2*5*7
S
S
*1*2*5
S
Ethernet device
1Gbps
100Mbps
*3
*3*6
SH
SH
*7
*7
SH
SH
*7
*7
SH
SH
*7
SH

Hide quick links: