(2) Precautions for laying cable
(a) Coaxial cables must be laid 100mm or more apart from power
cables and control cables.
(b) Consider wiring using double-shielded coaxial cable in places
that are subject to large amounts of noise.
Double shielded coaxial cable
Mitsubishi Cable ... 5C-2V-CCY
Grounding
The 5C-2V connector plug is applicable to double-shielded
coaxial cable.
Connect the 5C-2V connector plug to the coaxial cable inside a
double-shielded coaxial cable. Ground the shielded part outside
a double-shielded coaxial cable as shown in the above figure.
(3) Double shielded caoxial cables have the following restrictions on the
bending radius.
Allowable bending radius
Cable type
3C-2V
5C-2V
(4) Do not pull any of the connected coaxial cables.
This will cause a faulty contact, cable disconnection, or damage to
the unit.
(5) Make sure to connect a terminal resistor to both terminal stations of
the coaxial bus type network system.
(6) The F type connector has the possibility to extract a white oxide
according to the use enviroment.
However, there is no problem on the function because the oxide is
not generated in connected part.
Enlarged view
of cable
Internal
conducter
r [mm](in.)
23 (0.91)
30 (1.18)
13
Sheath
Insulation
External
material
conductor
Connector
A[mm](in.)
50 (1.97)
Sheath
External
conductor
(Grounding)
A