Mitsubishi Electric GOT1000 Series User Manual page 14

Communication unit for gt15-75j71lp23-z, gt15-75j71br13-z
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

No.
Name
1)
LED
A9GT-QJ71LP23
A9GT-QJ71BR13
Name
On : Normal operation
RUN
Off : The WDT error has Toccurred.
On : Set to the PLC to PLC network
PC
(Always ON)
On : Multiple transmission is being executed.
DUAL
Off : Multiple transmission is not being executed.
On : No.2 to 5 switch settings are incorrect.
SW.E
Off : Normal
On : Station No. settings are overlapped on the
M/S.E
same network.
Off : Normal
On : An error has occurred because common
parameters are inconsistent with station-
specific parameters, i.e., parameters
PRM.E
received from sub-control station are
different from those of host station
(received from control station).
Off : Normal
On : Power is supplied.
POWER
Off : Power is not supplied.
On : Data link is being executed.
D.LINK
Off : Data link is not being executed.
On : Participating in the button passing.
T.PASS
Off : Not participating in the button passing.
On : Communicating with GOT
GOT R/W
Off : Not communicating with GOT
On : An error has occurred, i.e., an error code is
detected in the received data.
<Cause> The timing when the station that
CRC
sends data to the corresponding station is
disconnected, H/W failure, cable failure,
noise, etc.
Off : Normal
On : An error has occurred, i.e., the received
data processing is delayed.
OVER
<Cause> H/W failure, cable failure, noise,
etc.
Off : Normal
5
Details
Details