Mitsubishi Electric MELSEC iQ-R Series User Manual page 56

High speed digital-analog converter module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Current output characteristic
The following shows the list of the analog output ranges and the graph of each current output characteristic, at the current
output.
I
20
(1)
4
0
-768
0
digit: Digital value
I: Analog output current (mA)
(a): Practical analog output range
No.
Analog output range setting
(1)
4 to 20mA
(2)
0 to 20mA
User range setting
*1 Set the offset value and gain value in the user range setting within a range that satisfies the following conditions. If the following
conditions are not satisfied, D/A conversion may not be performed properly.
Offset value  0mA, gain value  20mA
((gain value) - (offset value))  11.6mA
*2 Maximum resolution in the user range setting.
Set values within the practical range of the digital input and analog output at each output range. If the values
are out of the range, the resolution and accuracy may not fall within the range of the performance
specifications. (Do not use values in the dotted line regions in the graph of current output characteristics.)
APPX
54
Appendix 1 I/O Conversion Characteristics
(2)
32000
32767
Offset value
4mA
0mA
*1
(a)
digit
Gain value
Digital value
20mA
0 to 32000
20mA
*1
-32000 to 32000
Resolution
500.0nA
625.0nA
*2
360.0nA

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r60dah4-u-in-e

Table of Contents