External wiring example
The following figure shows the example of external wiring.
For voltage output
D/A
conversion
For current output
D/A
conversion
AG
*1 For the wire, use the 2-core twisted cable.
*2 In the event a noise or ripple occurs in the analog signal, connect a capacitor of 0.1 to 0.47F (withstand voltage of 25V or higher) to the
input terminal of external devices.
*3 Be sure to ground the FG terminal.
*4 If used within the analog output range of 0 to 5V, specify the external load resistance value at 500 or higher.
If used within the analog output range of -10 to 10V, specify the external load resistance value at 1k or higher.
Ground the FG terminal of the power supply module.
6 WIRING
28
6.2 External Wiring
*1
CH1
V+
COM
CH2
I+
COM
+24V
24G
Filter
FG
*2
Motor drive module or others
1kΩ or more/
500Ω or
more
*4
GND
GND
Motor drive module or others
50Ω
to
600Ω
GND
GND
24VDC
*3