Dual-Live Wire 208 V Power System; Overview - Huawei FusionModule500 Product Description

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Item
Output port
configuration
Rated output current
3.2.2 Dual–Live Wire 208 V Power System

3.2.2.1 Overview

The UPS supplies uninterruptible power to IT loads by means of batteries when the external
power supply fails.
Figure 3-7 Electrical conceptual diagram for the 208 V dual-live wire system configured with the
10 kVA/6 kVA UPS
Table 3-8 Power distribution system technical specifications
Item
Rated power
Rated input voltage
Rated frequency
Maximum input current
External input power
distribution circuit breaker
Issue 05 (2019-11-22)
Specifications
(Vertically
Installed
Full-Height
rPDU)
IEC: 20 x C13 + 4 x
C19
Chinese national
standards: 20 x 10 A
+ 4 x 16 A
32 A
Specifications (10 kVA
UPS)
8.1 kW
208 V
60 Hz
48 A
63 A
Copyright © Huawei Technologies Co., Ltd.
Specifications
(Vertically
Installed
Half-Height
rPDU)
IEC: 9 x C13 + 3 x
C19
Chinese national
standards: 9 x 10 A
+ 3 x 16 A
32 A
Specifications (6 kVA
UPS)
4.8 kW
208 V
60 Hz
31 A
50 A
3 System Architecture
Specifications
(Horizontally
Installed 1 U
rPDU)
IEC: 8 x C13
Chinese national
standards: seven
sockets that comply
with Chinese
national standards
16 A
28