Kva Ups - Huawei FusionModule500 Product Description

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Item
Maximum input current
Number of phases
Input power factor (full load)
input frequency
Total distortion of the input current
waveform (THDi)
Output voltage
Output frequency
Output power factor
Efficiency
Communications port (optional)
Dimensions (W x D x H)
Weight
Noise

3.2.1.3 6 kVA UPS

Figure 3-4 UPS2000-G
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
Specifications
19 A
1
> 0.99
Rated frequency: 50 Hz/60 Hz
Range: 40–70 Hz
< 5%
220 V/230 V/240 V
Tolerance: ± 1%
Normal mode: 50 Hz/60 Hz (± 6 Hz)
Battery mode: 50 Hz/60 Hz (± 0.05%)
0.9
94%
USB/RS485
430 mm x 615 mm x 86 mm
14 kg
< 55 dB
3 System Architecture
24

Advertisement

Table of Contents
loading

Table of Contents