FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Table 3-4 6 kVA UPS technical specifications
Item
Rated capacity
Maximum input current
Number of phases
Input power factor (full load)
input frequency
THDi
Output voltage
Output frequency
Output power factor
Efficiency
Communications port (optional)
Dimensions (W x D x H)
Weight
Noise

3.2.1.4 10 kVA UPS

Figure 3-5 UPS2000-G
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
Specifications
6 kVA
32 A
1
> 0.99
Rated frequency: 50 Hz/60 Hz
Range: 40–70 Hz
< 5%
220 V/230 V/240 V
Tolerance: ± 1%
Normal mode: 50 Hz/60 Hz (± 6 Hz)
Battery mode: 50 Hz/60 Hz (± 0.05%)
0.9
94%
USB/RS485
430 mm x 615 mm x 86 mm
14 kg
< 55 dB
3 System Architecture