FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Table 3-6 PDU5000 technical specifications
Item
Maximum input current
Number of phases
input frequency
Input voltage
Output frequency
UPS input
UPS output
UPS maintenance bypass
Output branch
Maximum altitude
Operating temperature
Humidity
Storage and transportation
temperature
Dimensions

3.2.1.6 rPDU

The rPDU is a basic socket, rather than a monitoring socket.
Table 3-7 rPDU technical specifications
Item
Rated current
Input frequency
Input port
Issue 05 (2019-11-22)
Specifications (3 kVA
UPS)
32 A
1
50 Hz/60 Hz
220 V/230 V/240 V
50 Hz/60 Hz
1-pole 32 A circuit breaker
1-pole 32 A circuit breaker
2-pole 32 A circuit breaker
2 x 16 A/1 P + 3 x 10 A/1 P
4000 m
–5° C to +40° C
5%–95% RH
–40° C to +70° C
430 mm x 450 mm x 130
mm
Specifications
(Vertically
Installed
Full-Height
rPDU)
32 A
50 Hz/60 Hz
Cord end terminal,
no input cable
Copyright © Huawei Technologies Co., Ltd.
Specifications (6 kVA
UPS/10 kVA UPS)
63 A
1
50 Hz/60 Hz
220 V/230 V/240 V
50 Hz/60 Hz
1-pole 63 A circuit breaker
1-pole 63 A circuit breaker
2-pole 63 A circuit breaker
4 x 40 A/1 P + 1 x 16 A/1 P
4000 m
–5° C to +40° C
5%–95% RH
–40° C to +70° C
430 mm x 450 mm x 130
mm
Specifications
(Vertically
Installed
Half-Height
rPDU)
32 A
50 Hz/60 Hz
Cord end terminal,
no input cable
3 System Architecture
Specifications
(Horizontally
Installed 1 U
rPDU)
16 A
50 Hz/60 Hz
Cord end terminal,
no input cable
27