Installing The Indoor Unit; Oil Trap And Inverted Trap (Unit: Mm); Mapping Between Saturation Temperatures And Pressure Of R410A - Huawei NetCol8000-A Series Quick Manual

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A Series:
Table of Contents

Advertisement

Mapping Between Saturation Temperatures and Pressure of R410A

Saturation
Gauge
temperature (º C)
(MPa)
10
0.99
11
1.02
12
1.05
13
1.09
14
1.12
15
1.16
16
1.19
17
1.23
18
1.27
2.2

Oil Trap and Inverted Trap (Unit: mm)

7/8 inch Oil trap
1 inch Gas pipe
inverted trap
3

Installing the Indoor Unit

1. Read the related user manual or instructions before installing the NetCol8000-A.
2. The unit in this document is a fully configured NetCol8000-A. If some components are not
configured, skip the corresponding steps.
3. You are recommended to use tools that are fully insulated when installing devices.
4. Only engineers from the manufacturer or engineers certified by the agent are allowed to
install, commission, and maintain smart cooling product. Otherwise, personal injuries and
device damage may be caused, which is beyond the smart cooling product warranty range.
Saturation
temperature (º C)
19
20
21
22
23
24
25
26
27
7/8 inch Gas pipe
inverted trap
4
Gauge
Saturation
(MPa)
temperature (º C)
1.31
28
1.35
29
1.39
30
1.43
31
1.47
32
1.51
33
1.56
34
1.60
35
1.65
36
3/4 inch Liquid
pipe inverted trap
Gauge (MPa)
1.69
1.74
1.79
1.84
1.89
1.94
1.99
2.05
2.10
1 inch Oil trap
5/8 inch Liquid
pipe inverted trap

Hide quick links:

Advertisement

Table of Contents
loading