Teamwork Settings - Huawei NetCol8000-A Series Quick Manual

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A Series:
Table of Contents

Advertisement

10.3
(Optional) Teamwork Settings
The table uses 8 smart cooling products in CAN teamwork as an example.
Item
Air
Teamwor
No.
condition
k group
er
no.
address
1
1
1
2
1
2
3
1
3
...
...
...
7
1
7
8
1
8
1. Teamwork group no.: A maximum of four groups, with the same teamwork control number, can be
assigned (1–4) for one teamwork networking.
2. Smart cooling product address: In a teamwork control group, each smart cooling product address
(1-32) must be unique, and the smart cooling product with minimum address is the master smart
cooling product.
3. Networking mode: The networking mode set on the screen must be consistent with the actual
networking mode.
4. Enable teamwork CAN resistor: Set the parameter if CAN teamwork is used. Set the parameter to
ON for the first and eight smart cooling products.
5. Number of smart cooling products in this group: Indicates the number of precision smart cooling
products in a group. The value is an integer ranging from 1 to 32.
6. Number of running smart cooling products in this group: Specifies the number of running
NetCol8000-As in a group. The value ranges from 1 to the number of NetCol8000-As in the group.
7. Rotation function: Enable the active and standby smart cooling products to work alternately. This
function is recommended when the heat load is even.
Enable
Teamwo
teamwor
Networking
rk
k CAN
mode
function
resistor
Yes
Enable
No
Enable
No
Enable
...
...
No
Enable
Yes
Enable
Number of
air
conditioners
in this group
CAN
8
network
CAN
/
network
CAN
/
network
CAN
...
network
CAN
/
network
CAN
/
network
32
Number of
running air
Rotation
conditioners
function
in this group
6 (2 standby)
Enable
/
/
/
/
...
...
/
/
/
/