GE Energy
Familiarization
, continued
Standard
The following table gives details of the standard chassis-mounted, auxiliary and
Power Supplies
redundant power supplies that are available. Other power supplies are available for
specific requirements. Contact GE Energy for details.
Type
Chassis-
mounted
Chassis-
mounted
Chassis-
mounted
Chassis-
mounted
Auxiliary
Auxiliary
Auxiliary
Auxiliary
Auxiliary
Redundant
Redundant
Redundant
Redundant
Redundant
D20/D200
Make sure your D20/D200 power input is externally protected for overcurrent. The
Overcurrent
fuse rating that is required depends on the specific power consumption of your
Protection
system.
General
Full
Part Number
Input
580-2004
20 – 60 VDC
580-2005
20 – 60 VDC
580-2006
100 – 300 VDC
or
85 – 264 VAC
580-2007
100 – 300 VDC
or
+85 – 264 VAC
521 - 0103
20 – 60 VDC
521 - 0104
100 – 300 VDC
521 - 0105
90 – 250 VAC
521 - 0106
100 – 350 VDC
521 - 0107
90 – 250 VAC
580 - 0719
110 VAC/125
VDC
580 - 0741
220 VAC/48
VDC
580 - 0789
110 VAC/ 48
VDC
510 - 0241
115 VAC + 15%
30 – 60 VDC
510 - 0242
115 VAC + 15%
40 – 144 VDC
Installation and Operations Guide
Output
+5 V, 7 A
+12 V, 2 A
-12 V, 1 A
24 VDC, 3 A
+5 V, 7 A
+12 V, 2 A
-12 V, 1 A
48 VDC, 1.5 A
+5 V, 7 A
+12 V, 2 A
-12 V, 1 A
24 VDC, 3 A
+5 V, 7 A
+12 V, 2 A
-12 V, 1 A
48 VDC, 1.5 A
24 VDC, 75 W
24 VDC, 75 W
24 VDC, 75 W
48 VDC, 120 W
48 VDC, 120 W
24 VDC
48VDC
48 VDC
48 VDC, 2.5 A
48 VDC, 2.5 A
994-0078-2.00-7
D20/D200
Mounting
Rack-mounted
Rack-mounted
Rack-mounted
Rack-mounted
Rack-mounted
Rack-mounted
Rack-mounted
27