Procedure: D20ME II - CCU (continued)
Step
Optional Step 2: To receive feedback during download
8
9
Download Code File
10
11
12
13
14
General
Full
, continued
Configure the HyperTerminal to communicate at the same speed, and
reconnect to the 68K Monitor.
If the communication software you are using does not have a "progress
indicator', you can enable echo to visually display the code file on the
monitor during transfer.
The echo option can be usually found in the Communication Settings or
Properties of the communication program.
Note:
Enabling echo may slow the transfer speed.
Type dl and press
ENTER
downloadable code file.
Click Transfer | Send Text File from menu bar
Result:
A dialog box opens, prompting you to locate the
Down.shx file that you wish to download.
Select the correct file, and click Open to start the transfer.
Result:
The file transfer may take from less than 10 minutes to
over 40 minutes, depending on the communication speed
selected.
When complete, the D20M> prompt returns.
Type el /p to display the error log.
Result:
The D20ME> prompt should return, indicating no errors
found.
Errors?
Record error(s), and re-try download.
If errors persist, contact GE for support.
Type el /r to ensure that log is clear, then type Boot to restart.
Result:
The D20ME II code download is complete.