9.11
Relay contacts: max. 2 A @ 30 V DC / 125 V AC (60W).
Connections and more information, see drawings 128-21 & -26.
The 3364 unit outputs VO0, VO1 & VO2
Each 3364 unit has two programmable, supervised (monitored)
voltage outputs:
VO0 Supervised (monitored) voltage output, 24V DC, max. 1A
VO1 Supervised (monitored) voltage output, 24V DC, max. 1A
VO2 is a voltage output, 24V DC, max. 1A
closing.
Normally high.
Technical Description MEW00529.
24 V DC required from an external power supply unit (e.g. 3366).
Connections, see drawing 128-21 & -28.
The 3377 / 4477 unit output (siren)
Each unit has one programmable output:
Output
Siren, with three priority levels and three sound types.
Connections and more information, see drawing 128-21.
The 3378 unit output (sounder)
Each 3378 unit has one programmable output:
Output
Sounder, with three priority levels and three sound types.
Connections and more information, see drawing 128-21.
The 3379 unit output (sounder)
Each 3379 unit has one programmable output:
Output
Sounder, with three priority levels and three sound types.
Connections and more information, see drawing 128-21.
The 4380 unit output (beacon)
Each 4380 unit has one programmable output:
Output
Beacon
Connections and more information, see drawing 128-21.
The 4383 unit output (Light indicator)
Each 4383 unit has one programmable output:
Output
Light indicator
Connections and more information, see drawing 128-21.