The smoke detector part has to be set to one of six alarm
algorithms H-15, H-35, L-15, L-35, N-15 or N-35 and the heat
detector part has to be set to one of three alarm algorithms for
class A1 (static response temp. 54-65°C), A2 S (54-70°C) or B
S (69-85°C). An alternative smoke and/or heat algorithm can
be used via one or two time channels.
2330 mode: 4400 in this mode will work as a 2330 + 2316/17.
2312 mode: Not used in system EBL128.
4301 Analog photo electric smoke detector. Replaced with 4401, see
below. Scattered light (i.e. reflection of infrared light) is used
to detect smoke.
The detector has unleaded soldering.
To be plugged in base 3312xx/3379/4313. Built-in LEDs are lit
to indicate that the detector has generated fire alarm. Prepared
for mechanical lock (screw attached).
The technical address is set with Address setting tool 3314 /
4414.
The detector has an address label on which the
programmed technical address is to be written.
The Address setting tool is also used for mode setting:
NORMAL mode: 4301 in this mode is in EBLWin set to one
of the six alarm algorithms H-15, H-35, L-15, L-35, N-15 or N-
35.
2330 mode: 4301 in this mode (+ base 3312) works like the
smoke detector 2321 (+ base 2330).
2312 mode: 4301 in this mode (+ base 3312) works like the
smoke detector 2304 (+ base 2312).
4401 Analog photo electric smoke detector.
above. Scattered light (i.e. reflection of infrared light) is used
to detect smoke. The detector has unleaded soldering. Shall be
plugged in base 3312xx/3379/4313. Built-in LEDs (red) are
blinking to indicate that the detector has activated fire alarm.
Prepared for mechanical lock (screw attached) – if required.
4401 has a little different design than the 4301 detector and the
smoke chamber net has even smaller holes that will keep insects
41
and particles
larger than smoke particles out of the chamber.
The COM loop address (Technical address) is set with Address
setting tool 3314 / 4414. The detector has an address label on
which the programmed technical address can be written. The
Address setting tool is also used for mode setting:
Advanced mode: 4401 has to be set to Advanced mode via the
Address setting tool 4414 . Note, the Address setting tool 3314
cannot be used to set Advanced mode! In Advanced mode this
detector will use algorithms in the detector for fire alarm
evaluation. It can be set to a Learning function or via EBLWin
to one of three area alarm algorithms (Normal, Clean or
Smoke/Steam area), see chapter "Advanced mode", page 123.
An alternative area alarm algorithm can be used via a time