Limitations - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
27
27.1

Limitations

C.i.e.
Max. number of "items":
Item
Fire alarms (presented in the EBL128
display as ZONE and/or ZONE-
168
ADDRESS)
Number of zones
Faults
External faults
Technical warnings
Short circuit isolators
Loop units
Trigger conditions (in all the control
expressions)
Interlocking Combinations
3377 + 3378 + 3379 + 4477 units
Total number of detectors and/or manual
call points
Max. number of AAF zones
Max. number of detectors per AAF zone
Max. number of I/O Matrix boards.
If no expansion boards.
Max. number of outputs per c.i.e. incl.
all kinds of outputs
Max. number of inputs
4380 units
168
Up to 256 ZONEs and/or ZONE-ADDRESSes can be programmed but
only the zone numbers 01-99 can be used.
169
Max. number of alarm points per c.i.e. (microprocessor) is 512 and max.
number of alarm points per zone is 32, i.e. if more than 12 conventional zone
line inputs are used, care must be taken in order not to exceed 512 detectors
and/or manual call points connected to the c.i.e. (12 x 32 = 384; 128 + 384 =
512).
172
EBL128 Planning Instructions V2.0.x
Max. no.
256
99
200
50
50
64
255
Approx.
1000
100
50
169
512
50
5
4
4+4
200
128
10