Panasonic EBL128 Planning Instructions page 165

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Other units
Routing equipment (Fire brigade tx / Fault tx)
External Presentation unit 1728
Alert Annunciation unit 1735 / 1736
External FBP 1826 / 1828
Printer 1835 (for ext. FBP 1826)
Alarm devices (sounders, etc.)
Door release magnets
Alert annunciation controller 1740
Rev: -
NOTE! Regarding the 1728, 1735, 1736, 1826, 1828 and 1835 units,
see the next page.
153
When the printer is active the current consumption is 161 / 345 mA
momentarily.
EBL128 Planning Instructions V2.0.x
Normal state
(quiescent) (mA)
Acc. to the producer
26@24 V / 48@12 V
26@24 V / 48@12 V
26@24 V / 48@12 V
153
4@24 V / 7@12 V
0
Acc. to the producer
10
163
Alarm state
(activated) (mA)
Acc. to the producer
49@24 V / 88@12 V
42@24 V / 79@12 V
49@24 V / 88@12 V
4@24 V / 7@12 V
Acc. to the producer
0
40