Panasonic EBL128 Planning Instructions page 166

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
The following table is a help when calculating the cable length and/or
the number of units. The table is based on the current consumption at
the lowest power supply voltage allowed i.e. 21 V DC by battery
back-up (no mains).
Recommended cable type is LIHCH-TP 2 x 2 x 0.75 mm
Wire resistance for this cable is approx. 25 ohm / 1000 m.
Up to four units can be connected but it is depending on the type of
units and the cable (type and length).
Number
Allowed cable resistance (ohm) / length (m)
of units
Units
1735, 1736
4
25 / 500
3
34 / 680
2
50 / 1000
1
100 / max. 1200
Explanation: 25 (ohm) ÷ 25 (ohm wire resistance per 1000 m) = 1000
m but the wire goes from the c.i.e. to the last unit and back to the c.i.e.
again, i.e. the cable length = 1000 (m) ÷ 2 = 500 m.
NOTE!
The table is based on the recommended cable type. If a cable with
greater area is used the wire resistance (ohm per 1000 m) will be
lower and the possible cable length will be longer.
It is also possible to use an external power supply, e.g. 3366, when a
greater number of units are required or if a longer cable length is
required.
154
Printing will only be performed if and when the door in the ext. FBP is
being opened. If the door is not opened until after all the alarms are reset,
there will be no printing.
164
EBL128 Planning Instructions V2.0.x
Units
1728, 1735, 1736,
1728, 1735, 1736,
1826, 1828 &
1826, 1828 &
no printers 1835
one
21 / 420
28 / 560
42 / 840
84 / max. 1200
2
.
Units
154
printer 1835
4 / 80
10 / 200
16 / 320
18 / 360